Bathroom Fan Code Requirements in Nova Scotia: Is a Fan Required?
For a new house in Nova Scotia, yes. The National Building Code of Canada 2020, which Nova Scotia uses without changing its fan clauses, requires a supplemental exhaust fan of at least 25 litres per second, about 53 CFM, in every bathroom or water-closet room that does not have an exhaust intake for the home's principal ventilation fan, such as an HRV grille. It must be switched from inside the bathroom and must exhaust to the outdoors, never into the attic. An openable window counts toward summer ventilation but does not replace the fan in a new house. For an existing home anywhere in Halifax Regional Municipality, By-law M-200 requires every bathroom or toilet room to have either an operable window or a mechanical exhaust fan kept in good working order.

A post in a Nova Scotia contractors' group asked it last week: do bathrooms here still need exhaust fans? The honest answer depends on the house, because two different rules apply. The building code decides what a new house needs, and it requires a fan. In existing homes in Halifax Regional Municipality, the HRM by-law sets the minimum standard, and it accepts a window instead. We read both. Below is what each says, clause by clause, plus the duct rules that decide whether the fan actually clears the room.
The short answer
Nova Scotia adopted the National Building Code of Canada 2020 from 1 April 2025. The province's Building Code Regulations change two things in the ventilation section, the principal ventilation rule and exhaust-only systems. They leave the bathroom fan clause alone, so the national text applies as written.
| Your situation | Does the bathroom need a fan? | What decides it |
|---|---|---|
| New house | Yes: at least 25 L/s (about 53 CFM), switched in the bathroom | Supplemental exhaust, 9.32.3.7.(4) and (6) |
| New house, window in the bathroom | Yes, still. The window covers summer ventilation, not winter | 9.32.1.2.(1) and Table 9.32.2.2. |
| New house, HRV exhaust grille in that bathroom | No separate fan for that bathroom | 9.32.3.7.(4) |
| Existing home in HRM | A working window or a working fan | HRM By-law M-200, section 19(2) |
| Renovation under a permit | The building official decides what the current code applies to | Permit scope |
| Existing home, no permit work | The building code isn't applied retroactively | Nova Scotia regulations, section 7(1) |
The rest of this page shows where each line comes from.
What the code says about new houses
The rule is in Article 9.32.3.7, Supplemental Exhaust, the same article that covers the kitchen fan:
"Where an exhaust air intake for the principal ventilation fan is not located in a bathroom or water-closet room, a supplemental exhaust fan with a rated capacity not less than 25 L/s shall be installed in that bathroom or water-closet room." (9.32.3.7.(4))
25 litres per second is about 53 CFM. That's the floor, and it's per room: a house with three bathrooms and no HRV grilles in them needs three fans. "Water-closet room" is code for a room with a toilet, so a powder room counts too.
The same article sets the controls:
- A switch in the bathroom. The fan "shall be controlled by a manual switch located in the room served by the fan" (9.32.3.7.(6)).
- Automatic controls are extras. If the fan also runs on a humidity sensor or timer, "the manual switch shall be capable of activating the fan regardless of the setting of the automatic control" (9.32.3.7.(8)).
Two more clauses decide which fan qualifies:
- How the 25 L/s is measured. Fan capacity is rated to a Canadian or HVI test (9.32.3.10.(1)), and for a fan like a bathroom fan, at 25 Pa of static pressure (Table 9.32.3.10.-A). The number has to hold against some resistance, not just in free air.
- How loud it can be. If there's less than 1 m of duct between the fan and the room, which describes most ceiling fans, it must be rated no louder than 2.5 sones on the CSA test or 3.5 sones on the HVI test (9.32.3.10.(6), Table 9.32.3.10.-B). The code's note gives the reason: fans need "reasonably low sound ratings so that building occupants will not turn them off before the need for ventilation has been met" (Note A-9.32.3.10.).
That last point is the whole game. A fan that's too loud gets switched off, and a fan that's switched off doesn't clear any moisture.
Does a window count instead of a fan?
In a new house, no. The code splits ventilation into two seasons:
- Summer ("non-heating-season") ventilation can be natural. A bathroom window counts if it gives at least 0.09 m² of unobstructed openable area, about one square foot (Table 9.32.2.2.).
- Winter ("heating-season") ventilation has to be mechanical in every house "supplied with electrical power and a heating system" (9.32.1.2.(1)(b)). The bathroom fan rule is part of that winter system (9.32.3.1.(2)(b)).
So the window satisfies one requirement and the fan satisfies the other. The code's notes explain why winter is the mechanical one: houses have become "progressively more airtight," and the concern is that natural air change "might be insufficient," with "condensation problems resulting from higher humidity levels" (Note A-9.32.3.).
In an existing home in HRM, a window can count. That's the by-law rule, below. In practice, though, a window you won't open in a Halifax January isn't ventilating anything, and shower moisture that can't leave ends up on the glass. We cover what that does in window condensation in winter.
When the HRV replaces the bathroom fan
The bathroom rule is written around the house's principal ventilation fan, which in most new Nova Scotia houses is an HRV. The fan is required "where an exhaust air intake for the principal ventilation fan is not located" in that bathroom (9.32.3.7.(4)). Flip it around: a bathroom with an HRV exhaust grille doesn't need its own fan. The code's note says the same: the bathroom is "another possible location for an air intake of a principal ventilation fan," and "if this option is not chosen, a separate bathroom exhaust fan must be installed" (Note A-9.32.3.7.).
Two conditions come with it:
- The grille goes high. HRV exhaust intakes in bathrooms go "in the ceiling or on the wall not less than 2 m above the floor" (9.32.3.3.(10)), because warm, moist air "tend[s] to rise and stratify near the ceiling" (Note A-9.32.3.3.(10)).
- It's per bathroom. An HRV grille in the main bathroom does nothing for the powder room downstairs. Each room without a grille still needs a fan.
One detail to settle on site. The code asks for a manual switch in an exempted kitchen or bathroom, wired to the HRV's control (9.32.3.7.(7)), but the sentences it points to are the kitchen ones. We'd put a boost switch in the bathroom anyway, because a bathroom you can't boost after a shower isn't much better than one with no fan, and we'd confirm the wiring with the building official. Our guide to whether an HRV is required in Nova Scotia covers the rest of the ventilation system.
Where the air has to go
A fan that blows into the attic meets the fan rule and fails the duct rules. The code is specific:
| The code asks for | What it means in your bathroom | Where |
|---|---|---|
| Never into an enclosed space | Not into the attic, a closed soffit or a joist space | 9.32.3.11.(2) |
| Insulated to RSI 0.5 through unheated space | A run across a cold attic is insulated, or the warm, moist air condenses inside the duct | 9.32.3.11.(3) |
| Duct reasonably airtight and impervious to water | A bathroom-only duct may be plastic, unlike most ducts, but it can't leak or soak up water | 9.32.3.11.(1) |
| Joints sealed with mastic, metal foil tape or the maker's sealant | Not cloth duct tape | 9.32.3.11.(8) |
| Supported, not crushed or sagging | No dips where condensation collects | 9.32.3.11.(7) |
| Outlet at least 1,800 mm from air intakes and vented soffits | The moist air can't be pulled straight back in by the HRV intake or through the soffit vents | 9.32.3.13.(4) |
| An outlet in a soffit only if that soffit is unvented, or blocked 1,800 mm each side | A cap tucked into a vented soffit puts the moisture into the attic | 9.32.3.13.(5) |
| A backdraft damper on the outlet | It closes when the fan stops, so cold air doesn't fall back down the duct | 9.32.3.13.(11) |
| Outlet at least 100 mm above the ground or roof surface below it | Clear of snow and splash | 9.32.3.13.(8) |
The attic is where this goes wrong most often, and the damage is slow and expensive. That's the subject of our guide to bathroom fan venting into the attic.
The duct table almost nobody quotes
Here's the rule we've never seen on a fan box. The code gives a table of the longest duct allowed for a given airflow, duct size and fan rating (Table 9.32.3.11.-A). For a bathroom fan delivering the code's 25 L/s at its rated 25 Pa:
| Round duct | Longest duct the table allows |
|---|---|
| 75 mm (3 in.) | None. Too small for 25 L/s at this rating |
| 100 mm (4 in.) | 2 m, about 6½ ft |
| 125 mm (5 in.) | 6 m, about 20 ft |
| 150 mm (6 in.) | 16 m, about 52 ft |
The length is measured from the grille in the bathroom to the hood outside (9.32.3.11.(10)). Two things move the numbers:
- A fan rated at higher pressure. If the fan is rated to deliver 25 L/s at 50 Pa, a 100 mm duct can run 6 m; at 62.5 Pa, 8 m (same table).
- Flexible duct. It has to go up a size, or be counted as twice its actual length (9.32.3.11.(11)).
This table isn't the only way to comply. The code allows ducts to be sized by the normal design method instead (9.32.3.11.(9)), and its note says the table "will generally result in very conservatively sized (i.e. larger) ducts" (Note A-9.32.3.11.). But it's a fair warning about the most common install there is: a standard fan on a long 4-inch duct to a roof cap often can't move the air it's rated for. If the mirror stays fogged with a fan that "works," that's usually why.
Houses with an oil furnace or a chimney
One more clause catches people. In a house with a fuel-fired furnace, boiler or water heater that vents up a chimney, the code requires exhaust devices other than the principal ventilation fan to be paired with an outdoor make-up air supply (9.32.3.8.(2)). Its note mentions bathroom fans by name: supplemental exhaust fans "are required to be coupled to supply fans of similar capacity" so they won't depressurize the house (Note A-9.32.3.7.). Houses with direct-vented or mechanically vented appliances, or a heat pump, fall outside it (9.32.3.8.(1)). How this works, and the three ways the requirement falls away, is in our make-up air guide.
Older houses, renovations and rentals
The building code isn't applied to an existing house just because it exists. Nova Scotia's Building Code Regulations say construction that lawfully existed before them is not required to conform "if the construction or condition does not constitute an unsafe condition in the opinion of a building official" (section 7(1)).
In HRM, the by-law sets the floor for existing homes. By-law M-200, Respecting Standards for Residential Occupancies, applies "to all residential occupancies within Halifax Regional Municipality" (section 1(1)), so owner-occupied homes as well as rentals. Section 19 says:
"Every bathroom or toilet room shall be equipped with: (a) an operable window; or (b) a mechanical exhaust fan which shall be maintained in good working order." (section 19(2))
It also says "all mechanical ventilation systems shall be maintained in good working order" (section 19(3)). A fan that's seized, disconnected or ducted to nowhere isn't in good working order. Outside HRM, check your own municipality's standards by-law.
New work is different. A renovation that opens walls is permit work in HRM, and then the building official decides what the current code applies to. Whether swapping a fan through the existing ceiling opening needs a permit is a question for HRM; the province's list of permit-free work doesn't name fans. Ask before you start.
Condos and apartment buildings are designed to other parts of the code. A new duct through an exterior wall is usually the condo corporation's or the landlord's decision.
Where we fit in
Bathroom exhaust is air-side ventilation work: the duct, the route through the attic or the wall, the insulation where it crosses a cold space, the sealed joints, and the exterior cap with its damper. That's our trade. New wiring and switches go to a licensed electrician.
We'll also tell you when the cheap answer is the right one. A fan that's too loud or too weak on a short, sound duct is a fan swap. A fan on a long, uninsulated 4-inch run to the attic is a duct job, and a new fan on the old duct won't fix it.
Sources
All code and by-law text quoted on this page was read in the published documents themselves on 2026-11-23, not taken from a summary.
Canadian sources
- National Research Council of Canada: National Building Code of Canada 2020, Volume 2, Division B (free from the NRC; second printing, including the revisions and errata released 31 March 2025). Cited: 9.32.1.2.(1) (non-heating-season ventilation for every residential occupancy; heating-season ventilation where there is electrical power and a heating system); Table 9.32.2.2. (0.09 m² natural ventilation area for bathrooms); 9.32.3.1.(2) (supplemental exhaust fans as a component of the heating-season system); 9.32.3.3.(10) (principal fan intakes in bathrooms at least 2 m up); 9.32.3.7.(4), (6), (7) and (8) (the 25 L/s bathroom fan, the manual switch, exempted rooms, automatic controls); 9.32.3.8.(1) and (2) (make-up air where fuel-fired appliances are not direct-vented or mechanically vented); 9.32.3.10.(1), (3) and (6), Tables 9.32.3.10.-A and -B (fan ratings, the 25 Pa rating pressure, sound limits); 9.32.3.11.(1) to (3) and (7) to (11), Table 9.32.3.11.-A (bathroom duct material, no discharge into enclosed spaces, RSI 0.5, support, sealing, duct sizing and lengths, flexible duct); 9.32.3.13.(4), (5), (8) and (11) (outlet clearances, soffits, height, backdraft dampers); and Notes A-9.32.3., A-9.32.3.3.(10), A-9.32.3.7., A-9.32.3.10. and A-9.32.3.11.
- Province of Nova Scotia: Building Code Regulations, read 2026-11-23 (the consolidation including N.S. Reg. 78/2026). Section 7(1) (existing buildings). In Section 9.32 the regulations amend Clause 9.32.3.3.(1)(b) and repeal Article 9.32.3.6. (exhaust-only systems), and nothing else; they do not amend Article 9.32.3.7., 9.32.3.11. or 9.32.3.13. The list of work needing no permit (section 9(2)) does not mention fans. Adoption of the 2020 codes from 1 April 2025: news release, 20 September 2024.
- Halifax Regional Municipality: By-law M-200, Respecting Standards for Residential Occupancies, read 2026-11-23 (in force 23 July 2016, amended by M-201 and M-202, the latter effective 15 April 2023). Sections 1(1) (applies to all residential occupancies in HRM), 19(2) (window or exhaust fan) and 19(3) (mechanical ventilation maintained).
Every source on this page is Canadian. We used no non-Canadian source.
What we could not source, and what we left out
- The CSA ventilation standard. The code lets a designer meet the ventilation requirements through CAN/CSA-F326-M instead of the prescriptive rules on this page (9.32.3.1.(1)(a)). It's a paid standard and we haven't read it, so a house designed to it may be laid out differently.
- Whether HRM requires a permit to replace or add a bathroom fan. Neither HRM's by-law nor the province's permit list addresses it by name.
- The wiring. Circuits, switches and fan-light-heater combinations are electrical work under the Canadian Electrical Code, which we haven't covered.
- Municipalities outside HRM. Their housing standards by-laws, if any, may differ from M-200.
- Any cost. It depends on the ceiling, the route and the outlet, and we don't publish prices before seeing the house. Our bathroom fan installation guide explains what drives the price.
Related services
Frequently asked questions
Is a bathroom fan required by code in Nova Scotia?
In a new house, yes, unless the bathroom has an exhaust intake for the home's principal ventilation fan, such as an HRV grille. The National Building Code of Canada 2020, which Nova Scotia uses, requires a supplemental exhaust fan of at least 25 litres per second, about 53 CFM, in every bathroom or water-closet room without one, controlled by a manual switch in that room. Nova Scotia's Building Code Regulations do not change that clause.
Is it illegal to have a bathroom without a fan in Nova Scotia?
Not if it has a window that opens, in an existing home in Halifax Regional Municipality. HRM By-law M-200 applies to all residential occupancies in the municipality and requires every bathroom or toilet room to have an operable window or a mechanical exhaust fan maintained in good working order. A bathroom with neither does not meet the by-law. New construction is held to the building code, which requires the fan.
Do you need a bathroom exhaust fan if you have a window?
In a new house, yes. The building code counts an openable bathroom window of at least 0.09 square metres toward non-heating-season ventilation, but heating-season ventilation has to be mechanical, and that is where the 25 litre per second bathroom fan requirement sits. In an existing home in HRM, By-law M-200 accepts a working operable window instead of a fan. Either way, a window nobody opens in January does not clear shower moisture.
What size bathroom fan does the code require in Canada?
The National Building Code of Canada 2020 sets a minimum rated capacity of 25 litres per second, about 53 CFM, measured at 25 pascals of static pressure. Where the fan is mounted with less than 1 metre of duct between it and the room, it must also be rated no louder than 2.5 sones on the CSA test or 3.5 sones on the HVI test. Provinces adopt the code themselves, so check your own province's version.
Can a bathroom fan vent into the attic or a soffit?
Not into the attic. The code says exhaust ducts shall not discharge into heated or unheated enclosed spaces, and a duct crossing a cold attic has to be insulated to at least RSI 0.5. The outlet must be outdoors, at least 1,800 millimetres from air intakes and vented soffits, with a backdraft damper. An outlet in a soffit is allowed only if that soffit is unvented, or blocked for 1,800 millimetres on each side of the outlet.
Does an HRV replace a bathroom fan?
It can. The code requires a separate bathroom fan only where an exhaust air intake for the principal ventilation fan is not located in that bathroom. If the HRV draws exhaust from the bathroom through a grille in the ceiling or on the wall at least 2 metres above the floor, that bathroom does not need its own fan. Every bathroom without an HRV intake still does.